FLAT STATIONS

Our tubra®
flat stations FSM / FSU

Thermostatically controlled flat stations with domestic hot water outputs from 35 to 50 kW and primary flow rates from 720 to 1,180 l/h at maximum hot water output.

tubra® flat stations FSM / FSU

tubra®-FSU / FSM

The thermostatically controlled tubra®-FSU / FSM flat stations provide convenient, decentralised and hygienic potable water heating and efficient heat distribution.

Suitable for new buildings and refurbishment projects, with extensive standard equipment. Versions are available for radiator systems, underfloor heating and combinations of both.

All versions are available with copper-brazed or all-stainless-steel brazed plate heat exchangers.

  • Output range from 35 to 50 kW.
  • Thermostatic hot water control via a three-way priority control valve.
  • Standby temperature of 50°C in accordance with VDI 2072.
  • Hot water comfort levels.

tubra®-Varianten FSU und FSM

The flat stations are available in various configurations for unmixed and mixed heating circuits, with or without a high-temperature connection.
 
Unmixed heating circuit
 
  • tubra®-FSU-S (14 l/min), copper-brazed heat exchanger.
  • tubra®-FSU-S (14 l/min), all-stainless-steel heat exchanger.
  • tubra®-FSU-M (20 l/min), copper-brazed heat exchanger.
  • tubra®-FSU-M (20 l/min), all-stainless-steel heat exchanger.
Mixed heating circuit
 
  • tubra®-FSM-S (14 l/min), copper-brazed heat exchanger.
  • tubra®-FSM-S (14 l/min), all-stainless-steel heat exchanger.
  • tubra®-FSM-M (20 l/min), copper-brazed heat exchanger.
  • tubra®-FSM-M (20 l/min), all-stainless-steel heat exchanger.
 
Mixed heating circuit with high-temperature connection
 
  • tubra®-FSM HT-S (14 l/min), copper-brazed heat exchanger.
  • tubra®-FSM HT-S (14 l/min), all-stainless-steel heat exchanger.
  • tubra®-FSM HT-M (20 l/min), copper-brazed heat exchanger.
  • tubra®-FSM HT-M (20 l/min), all-stainless-steel heat exchanger.

Product range

Flat station with hot water circulation

tubra®-FSU / FSM

Hot water flow rate: 14–20 l/min at 60°C primary supply temperature, 10°C cold water inlet temperature and 45°C hot water outlet temperature.

Flat station without hot water circulation

tubra®-FSU / FSM

Hot water flow rate: 14–20 l/min at 60°C primary supply temperature, 10°C cold water inlet temperature and 45°C hot water outlet temperature.

tubra® – a selection of accessories

tubra® FSU and FSM configurations

Output ratingsNetwork temperature: 60°C. Hot water temperature: 45°C.
 
  • FSU/M-S: 14 l/min (35 kW).
  • FSU/M-M: 20 l/min (50 kW).
 
Dimensions
 
  • Installation depth of 110 mm, suitable for dry-lined walls.
  • Narrow surface-mounted housing: 570 × 700 × 150 mm.
  • Narrow flush-mounted housing: 570 × 700–900 × 110–160 mm.
  • Wide surface-mounted housing: 700 × 1,160 × 150 mm.
  • Wide flush-mounted housing: 700 × 1,160–1,350 × 110–160 mm.
 
Thermo Comfort System
 
  • Thermostatic hot water control via a three-way priority control valve.
  • Standby temperature of 50°C in accordance with VDI 2072.
  • Hot water comfort level III in accordance with VDI 6003.
 
Delta Control System
 
  • Integrated differential pressure controller, 30 kPa.
  • Presettable zone valve in the heating outlet.
 
Safety Set
 
  • Strainer at the station inlet.
  • Water hammer arrestor.
  • Manual air vent in the flow line.
Measurement Ready
 
  • Spacer piece for a heat meter, 110 mm / ¾“.
  • Spacer piece for a cold water meter, 110 mm / ¾“.
 
Circulation Set
 
  • Connection for a domestic hot water circulation pump.
  • Suitable for pumps such as the Lowara Ecocirc 15/1 with an integrated thermostat.
  • Can be controlled by a timer.
 
Mixed Heating System – 10 kW
 
  • Connection for a mixed underfloor heating circuit with thermostatic constant temperature control.
  • Maximum underfloor heating circuit output: Q = 10 kW, ΔT = 5 K, 1.7 m³/h.
  • A thermostatic head with a remote sensor controls the flow rate from the network and maintains the selected flow temperature between 20 and 50°C.
  • Temperature switch in the underfloor heating flow line, maximum 55°C.

 

High Temperature Radiator Option

  • Additional high-temperature outlet for a bathroom radiator, with return temperature limitation.

  1. Copper-brazed plate heat exchanger (Cu), optionally all-stainless-steel (VE).
  2. Thermostatic head for the three-way control valve.
  3. Thermostatic three-way control valve with hot water priority.
  4. Water hammer arrestor.
  5. Thermostatic return temperature limiting valve for hot water preparation.
  6. Thermostatic head for return temperature limitation, with a copper coil sensor.
  7. Heating zone valve M30 × 1.5 for the mixed heating circuit.
  8. Electrothermal actuator.
  9. Heating zone valve for the mixed heating circuit, with an injection circuit arrangement.
  10. Thermostatic head with a remote sensor for constant flow temperature control in the mixed heating circuit (20–50°C).
  11. Return temperature limiting valve for the unmixed heating circuit.
  12. Thermostatic head M30 × 1.5 for return temperature limitation.
  13. High-temperature outlet for a bathroom radiator (second heating circuit).
  14. Underfloor heating circulation pump for the mixed heating circuit.
  15. Pipe-mounted thermostat acting as a safety temperature limiter to prevent excessive flow temperatures in the mixed heating circuit.
  16. Differential pressure controller, 30 kPa.
  17. Spacer piece for a heat meter, ¾“ × 110 mm.
  18.  
  1. Strainer with a pressure tapping point for the differential pressure controller and an M10 × 1 connection for the heat meter flow temperature sensor.
  2. Spacer piece for a cold water meter, ¾“ × 110 mm.
  3. Circulation Set including a pump, safety valve and ball valve (optional accessory).
  4. Mounting connection plate with seven or nine ball valves (optional accessory).

Connections

A: PWH-C* – Domestic hot water circulation
B: PWC* – Cold potable water, dwelling
C: PWC* – Cold potable water, primary
D: PWH* – Domestic hot water
E: HV – Primary heating water flow
F: HR – Primary heating water return
G: HR – Mixed heating water return
H: HV – Mixed heating water flow
I: HR – Unmixed heating water return
J: HV – Unmixed heating water flow

Abbreviations in accordance with DIN EN 806 Part 1.

PWC: Potable Water Cold – colour coding: green.
PWH: Potable Water Hot – colour coding: red.
PWH-C: Potable Water Hot Circulation – colour coding: purple.

You may also be interested in

Our tubra®-eTherm products

Use surplus PV electricity efficiently to generate heat and increase your self-consumption. With eTherm, you can turn solar electricity into space heating and hot water – intelligently, flexibly and perfectly tailored to modern heating systems.